Potential monitoring device as per DIN EN 50122 part 1 / VDE 0115 part 3
As protection from dangerous body currents generated from contact voltages/tapping voltages,
maximum voltages have been stipulated depending on the effect time.
Technical Data
Dimensions
W / H / D 150 / 73 / 113 mm
Housing material
Terminal board: polycarbonate
lower section: ABS
Fastening
2 drilled holes as per drilling tem-
plate Standard support rails as per
DIN EN 50022
Protection
Housing: IP 40; terminals: IP 10
Connections
2 x 2.5 mm2 solid to DIN 46288 or
2 x 1.5 mm2
Ambient temp.
- 20°C to + 60°C
Power supply
AC 19.2 ... 253 V, 50 – 60 Hz, ? 5.5
VA
DC 19.2 ... 253 V, ? 2.5 W
Measuring input
? 1500 V, continuous; resistance:
approx. 2 M?
Relay outputs
2 change-over contacts (u), poten-
tial-free
voltage current cos ?
AC 250 V4.0 A > 0.7
DC 120 V 1.0 A ohmic load
Displays
Network LED green
K1: LED yellow
K2: LED yellow
voltage level: bar graph array
Test voltage
Supply voltage - measuring voltage
outputs: 6 kVe?
Input voltage
DC 50 V < UM < DC 90 V
K1 switches after 295 ... 299 s
(workshop)
DC 100 V < UM < DC 140 V
K1 and K2 switch after 295 ... 299 s
UM > DC 140 V
K1 and K2 switch jointly as per
diagram
UM > DC 660 V
K1 and K2 switch after max. 30 ms
AC 25 V < UM < AC 40 V
K1 switches after 295 ... 299 s
(workshop)
AC 50 V < UM < AC 70 V
K1 and K2 switch after 295 ... 299 s
UM > AC 70 V
K1 and K2 switch jointly as per diagram
UM > AC 842 V
K1 and K2 switch after max. 30 ms
Diagram
see overleaf
Ordering Information
Type 8521
Order No. 210100