Varec
Varec 8130 Remote Terminal Unit
Contact with us! 24 business hours (excluding weekends and holidays) to confirm stock status and estimated delivery time.
The 8130 Remote Terminal Unit (RTU) collects and transmits data from field instruments to a central system, such as FuelsManager®, host DCS or PLCs. All information obtained can be used for inventory, alarm, control and automation.
Specifications
PowerSupply – 110–120 V AC or 200–240 V AC @ 50/60 Hz or 18–36 V DC
Consumption – 50 VA max @ 110/220 VAC (500 mA), 20 VA max @ 24 VDC
Operating Temperature Range
?40 to +158 °F (?40 to +70 °C)
Approvals
FM ? Class I, Division 2, Groups A, B, C & D T3C (with optional NEMA 4 enclosure required)
CSA ? Class I, Division 2, Groups A, B, C & D (with optional NEMA 4 enclosure required)
Options
01 Power Supply
110…120 V AC 50/60 Hz 220…240 V AC 50/60 Hz 18…36 V DC
02 Host Emulation
None TSU Emulation ? for connection to Varec TankView systems CIU Emulation ? emulates Enraf model 858 CIU interface
03 Field Communications
None Varec Matrix Communication ? interfaces to Varec Matrix devices (1600/1700) require 8210, 8201 & 8204 Interface Modules MODBUS Master Communication* CIU communication ? interfaces to existing Enraf 858 CIU devices* Veeder Root (TLS 350) Communication* Hectronic OptiLevel Communication*
Note! * Using RTU motherboard communications ports
04 Calculations
None Hybrid tank calculations Hydrostatic tank calculations
05 Strapping Tables
None Embedded tank strapping tables Floating Roof Tank with Floatwell Tank Top Mounting Bolted Tank Cone Roof Tank with Pan (No Floatwell) Floating Roof Tank (No Floatwell
06 Approvals
For use in non?hazardous areas FM ? Class I, Division 2, Groups A, B, C & D T3C (with optional NEMA 4 enclosure required) CSA ? Class I, Division 2, Groups A, B, C & D (with optional NEMA 4 enclosure required)
INTERFACE MODULES
16-Channel Digital I/O
Interface Module 8201
16 digital I/O channels 24 VDC, 120 or 240 VAC Channels individually configurable for input or output Dedicated status LED Dedicated fuse for output modules only Requires two I/O expansion module slots
MODBUS Dual RS-485
Interface Module 8203
Dual high-speed communications channels Optically isolated Up to 32 devices per channel Communications with instruments using Rackbus, MODBUS, DDA, or Petrosense Probe protocols Requires one I/O expansion module slot
8 Channel Multi-Function
Interface Module 8204
Isolated analog (4-20 mA), Thermocouple, RTD inputs, high speed pulse accumulation or digital I/O channels 24 VDC, 120 or 240 VAC operation Individually configurable for input or output Dedicated status LED/fuses Requires one I/O expansion module slot
16 Channel Analog Input
Interface Module 8205
12 bit accuracy A/D with common-mode noise rejection Dedicated fused 24V line for each channel Throughput accuracy (field to database) = ±0.012%. Each channel individually configurable for; 4-20 mA loop powered input, 4-20 mA self powered, voltage input Requires two I/O expansion module slots
8-Channel Analog Output
Interface Module 8207
16 Bit accuracy D/A converter Current or voltage level output (0-24 mA, 0-20 mA, 4-20 mA & 0-5V) 8 channels Requires one I/O expansion module slot
TIWAY (Texas Inst.)
Interface Module 8208
Dual high-speed communications channels Optically isolated Up to 32 devices per channel Communications using TIWAY or CIM protocol Requires one I/O expansion module slot
Mark/Space (Varec)
Interface Module 8210
Supports up to 50 tanks Communicates using Mark/Space protocol Interfaces to the Varec 1900 and compatible tank gauge transmitters Requires one I/O expansion module slot
Current Loop
Interface Module 8211
20 mA current loop Up to 15 devices per channel Two channels Communicates using GPE or Whessoe Bus protocol Requires one I/O expansion module slot
TRL/2 (SAAB)
Interface Module 8212
Saab (Emmerson) TRL/2 Bus Up to 16 Saab Radar Tank Gauges per channel Two channels Requires one I/O expansion module slot
BPM (Enraf)
Interface Module 8214
Transformer isolated Up to 10 tanks per channel Two channels Communications with Enraf tank gauges Requires one I/O expansion module slot
Tankway (L&J)
Interface Module 8215
Supports up to 50 tanks Communicates using L&J Tankway protocol Interfaces to L&J Tankway compatible tank gauge transmitters Requires one I/O expansion module slot
LON (Prime/Barton)
Interface Module 8216
Supports up to 128 tanks Communicates with LON Series 3500 TCU 78 Kbps twisted pair LON interface Requires one I/O expansion module slot
Dual RS-232
Interface Module 8217
Dual high-speed communications channels RS-232 communications Communicates with L&J Model 8100 Communicates with Veeder Root TLS-350 Communicates with Universal Sensors & Devices CATLAS Communicates with Enraf CIU Communicates with MODBUS devices Requires one I/O expansion module slot
01 Power Supply