Output Signal |
Standard 2-wire: 4-20 mA / Vs = 8-32 Vdc
Optional 3-wire: 0-10 V / Vs = 14-30 Vdc
Optional 3-wire ratiometric: Vsig = 0.5-4.5 V / Vs = 5 ± 0.5 Vdc
|
Accuracy |
±0.5% FSO |
Permissible Load |
2-wire: Rmax = [(Vs – Vs min) / 0.02] Ohm
3-wire: Rmin = 10 kOhm
|
Influence Effects |
Supply: 0.05% FSO / 10 V
Load: 0.05% FSO / kOhm
|
Response Time |
2-wire: <10 ms
3-wire: <3 ms
|
Measuring Rate |
1 kHz |
Thermal Error |
<±0.3% FSO / 10K in compensated range 32°F to 158°F (0°C to 70°C) |
Permissible Temperatures |
Medium: -13°F to 185°F (-25°C to 85°C)
Electronics environment: -13°F to 185°F (-25°C to 85°C)
Storage: -40°F to 185°F (-40°C to 85°C)
|
Short-circuit Protection |
Permanent
3-wire ratiometric: None
|
Reverse Polarity Protection |
No damage. No function. |
Electromagnetic Protection |
Emission and immunity according to EN 61326 |
Stability |
Vibration: 10 g, 25 Hz to 2 kHz according to DIN EN 60068-2-6
Shock: 100 g / 1 ms according to DIN EN 60068-2-27
|
Pressure Port / Housing |
304 SS |
Wetted Parts |
Seals: FKM (standard)
Diaphragm: 316L SS
|
Weight |
120 g |
Current Consumption |
2-wire: 25 mA max
3-wire voltage: 5 mA (short-circuit current 20 mA)
3-wire ratiometric: 1.5 mA
|
CE Conformity |
EMC directive: 2004/108/EC |